Siemens S7-1200/1500 Settings

Software used: TIA Portal V16

Software connection to PLC

First, the connection device settings should be made, as shown in the image below. connection

  1. Under the device name, double-click Device configuration, and select Ethernet addresses in the interface directory.
  2. Fill in the IP address of the network connected to the PLC correspondingly to complete the connection setting.

Check slot and rack

Under the condition that the software is correctly connected to the device, on the Device configuration page, select General -> Project information to view the rack number and slot number, as shown in the image below. slot-rack

PLC Setting

The following settings are also required when accessing an S7 1200/1500 PLC.

First, to close the access to the optimization block

Right-click the DB block that you want to use, and select Properties in the pop-up dialog box, as shown in the image below. db-setting

In the dialog box that pops up, uncheck Optimized block access, as shown in the image below. db-optimied

Second, PLC security settings

Right-click the device name, and select Properties in the pop-up dialog box, as shown in the image below. plc-setting

First, set the Access level, and set the read and write permissions according to your needs, as shown in the image below. plc-permission-control

Then set Connection mechanism, check Permit access with PUT/GET communication from remote partner, as shown in the image below. plc-access-control